电气预埋规范

电气预埋规范

ID:39770560

大小:50.51 KB

页数:3页

时间:2019-07-11

电气预埋规范_第1页
电气预埋规范_第2页
电气预埋规范_第3页
资源描述:

《电气预埋规范》由会员上传分享,免费在线阅读,更多相关内容在行业资料-天天文库

1、电气埋管施工工艺细则Electricalconduitconstructiontechnologyrules1.严禁使用电焊、气焊割管。Strictlyprohibitedinusinggasandelectricweldingcuttingconduit.2.严禁将脚手架作为电缆管使用。Strictlyprohibitedinusingthefolderaselectricalconduit.3.锈蚀严重的钢管不得使用;钢管弯制或安装前应将管口及管内杂物清扫干净,并除去毛刺。Existseriouscorrosionconduitisnotall

2、owedused;themouseoftheconduitastheinnerpartthedebrismustberemovedbeforebendingorinstallation3.电缆管切割采用手工锯或切割机进行切割,并保证切割面平整且不倾斜;切割后必须立即将管口毛刺打磨干净,并打磨管口成喇叭型。Cuttingfortheconduitadoptinginmanualsawormachine,andensurethecuttingsurfacesmoothandnottilt;burringaftercuttingmustbeimmedia

3、tely,andpolishedtypenozzleintohorn.4.电缆管的弯曲半径R≥10D(电缆管外径);弯曲角度≥90°,并尽可能减少90°弯头;电缆管弯制不得出现明显的凹瘪、裂纹、折皱,钢管弯扁程度≤0.1D(电缆管外径)。BendingradiusR≥10D(hereDisconduitoutdiameter);BendingAngle≥90°,andaslessaspossiblethe90°elbow;conduitbendingcannotappearobviousconcave,crack,wrinkle,flatsteel

4、tubebendingflatlevel≤0.1D(hereDisconduitoutdiameter).6.电缆管安装时,每根电缆管弯头数量不得超过3个,90°弯头不得超过2个(埋管长度≥12米,不得多于2个弯头;12米≥埋管长度≥8米,不得多于3个弯头;直管埋设不得大于30米)超过上述标准须增加转接盒。Wheninstallationconduit,theamountofeachconduitelbowshallnotexceed3,elbowwith90°shallnotbemorethan2;theconduitlength≥12m,sha

5、llnotbemorethantwoelbow;Thelengthoftheconduitthatchangedbetween8mand12m,shallnotbemorethanthreeelbow;straightshallnotbemorethan30meters;Ifexceedthestandardmorethanthestandardmustincreasethetransferbox.7.电缆管连接不得对接焊,必须采用短套管;套管长度≥50mm;whenconduitconnectionashortsocketmustbeused,a

6、ndnobuttwelding(exceptspotwelding);thelengthofthesocketmorethan2timesofconduitoutdiameter.电缆管型号Type壁厚(mm)Thickness电缆管外径(mm)Outdiameter.连接套管内径(mm)Socketinner连接套管的长度(mm)LengthdiameterDN253.2533.535≥50mmDN323.2542.343≥50mmDN503.56061≥50mmDN8048889≥50mm8.电缆管连接时,先将套管中间凸台毛刺打磨干净,然后将电

7、缆管插入套管中,电缆管与凸台之间不得留有间隙;连接套管与电缆管两侧均匀电焊4点,并用黑胶布缠绕封实;Whencoupling,thereshouldn’tgapbetweenthetwoconduitandthecounterpartmalocclusionislessthan2mm,counterpartseamshouldbeinthemiddleofthesocket,andthebothsidesalongthecircumferentialweldingsealing,partialcannotweldingmustuseblacktap

8、ewindingsealingwithfastenedironwire;9.电缆管不得在外壁直接点焊加固,加固采用铁丝绑扎

当前文档最多预览五页,下载文档查看全文

此文档下载收益归作者所有

当前文档最多预览五页,下载文档查看全文
温馨提示:
1. 部分包含数学公式或PPT动画的文件,查看预览时可能会显示错乱或异常,文件下载后无此问题,请放心下载。
2. 本文档由用户上传,版权归属用户,天天文库负责整理代发布。如果您对本文档版权有争议请及时联系客服。
3. 下载前请仔细阅读文档内容,确认文档内容符合您的需求后进行下载,若出现内容与标题不符可向本站投诉处理。
4. 下载文档时可能由于网络波动等原因无法下载或下载错误,付费完成后未能成功下载的用户请联系客服处理。